Symmetra PX 64kW Scalable to 160kW, 400V SY64K160H

Availability:

On Order Only


  • Modular, high-efficiency 3-phase UPS that is scalable as your data center grows up to 160kW/160kVA. Suitable for small, medium & large data center applications.

  • Includes: Network management card, Start-up service, User manual

Output

Max Configurable Power (Watts)

160.0kWatts / 160.0kVA
Neutral Output Current

160A
Output Voltage Note

Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load

95.0 %
Output Voltage Distortion

Less than 2 %
Output Frequency (sync to mains)

50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz Sync to mains
Topology

Double conversion online
Waveform type

Sine wave
Overload Operation

10 minutes at 125% and 60 seconds at 150%
Output Voltage THD

< 2% for 0 to 100% linear load and < 6% for full non-linear load
Output Voltage Tolerance

+/- 1% static and +/- 5% at 100% load step
Bypass

Built-in static bypass

Input

Input frequency

40 – 70 Hz
Input voltage range for main operations

340 – 460 (400 V) Adjustable, 340 – 477V
Efficiency at Full Load

95.0 %
Input Total Harmonic Distortion

Less than 5 % for full load
Maximum Short Circuit Withstand (Icw)

30.0kAmps
Input Power Factor at Full Load

0.99

Batteries & Runtime

Battery type

VRLA
Included Battery Modules

6
Typical recharge time

3.5hour(s)
Nominal Battery Voltage

+/- 192 V (split battery referenced to neutral)
End of Discharge Maximum Battery Current

221.0A
Battery Slots Empty

3
RBC Quantity

4
Battery Charge Power (Watts)

5.908kWatts
DC Overcurrent Protection

320A
Extendable Run Time

1
End of Discharge Battery Voltage

+/- 154 V
Efficiency in Battery Operation

94.0 %
Maximum Available Short Circuit Current

4kAmps
Overload Operation

10 minutes at 125% and 60 seconds at 150%

Communications & Management

Interface Port(s)

DB-9 RS-232, SmartSlot
Control panel

Multifunction LCD status and control console
Audible Alarm

Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)

Yes

Physical

Maximum Height

1991MM, 199.1CM
Maximum Width

1200MM, 120.0CM
Maximum Depth

1070MM, 107.0CM
Net Weight

1388.0KG
Shipping weight

1511.0KG
Shipping Height

2140MM, 214.0CM
Shipping Width

1696MM, 169.6CM
Shipping Depth

1210MM, 121.0CM
Color

Black

Environmental

Operating Temperature

0 – 40 °C
Operating Relative Humidity

0 – 95 %
Operating Elevation

0 – 1015.9meters
Storage Temperature

-15 – 40 °C
Storage Relative Humidity

0 – 95 %
Storage Elevation

0 – 15240meters
Audible noise at 1 meter from surface of unit

63.0dBA
Online thermal dissipation

11496.0BTU/hr
Protection Class

IP20, NEMA 1

Conformance

Approvals

EN 50091-1, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, EUROBAT, ISO 14001, ISO 9001, VFI-SS-111
Standard warranty

1 year on-site repair or replace with factory authorized Start-Up

General

Bypass Connection

5 wire (3P + N + E)
Bypass Protection Device

250.0
Max Bypass Input Current

250.0A
SKU: SY64K160H Category: